1.5kVA on-line double-conversion UPS with tower and interactive LCD display. Ideal for critical server and network equipment in a variety of application environments. Maintains perfectly regulated output power by continuously converting raw AC input to DC, then re-converting output back to AC. Sine wave AC output with +/-2% voltage regulation powers network equipment continuously, even during severe brownouts and overvoltages, all without depleting UPS battery reserves. Maintains battery-derived AC output during power failures with zero transfer time. Extended runtime options available.
Two switched output load banks support remote reboot and programmable load shedding options
Supports 2% output voltage regulation and zero transfer time in double conversion mode
Economy mode option offers high 97% efficiency, reduced power consumption and lower BTU emissions
14 minutes runtime at 50% load (675W) and 4.5 minutes at 100% load (1350W) with internal batteries
Extended runtime options available with BP48V24-2U (limit 1) or BP48V60RT3U (no limit) external battery packs (external battery configurations require external battery configuration software)
Single line TEL/network surge suppression
Electronic bypass maintains utility output during a variety of UPS fault conditions
Frequency regulation/conversion mode offers generator-compatible frequency correction or conversion of frequency from 50 to 60Hz or 60 to 50Hz
Built-in USB, RS-232, contact-closure and optional SNMPWEBCARD accessory monitoring options
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software
Warranty - Yes
UL Rated - Yes
Spec Sheet available - Yes
Operating Temperature (Maximum):
40 C
Operating Temperature (Minimum):
0 C
Estimated Runtime:
4.50 minutes
Output volt amp capacity:
1500 VA
Output Watt Capacity:
1350 W
Nominal Output Voltage (Supported):
100/110/120/127 V
Frequency Compatibility:
50/60 Hz
Built-in UPS output receptacles:
6 x 5 to 15R outlets
Rated input current (at maximum load):
12 A
Nominal Input Voltage (Supported):
100/110/120/127 VAC
Input Connection Type:
5 to 15P
Battery Full Load Runtime:
4.5 minutes (1350W)
Battery Half Load Runtime:
14 minutes (675W)
DC Battery System Voltage:
48 VDC
Primary Form Factor:
Tower
Shipping Dimensions:
15.2 x 13 x 24 inches
UPS housing material:
Steel
Cooling Method:
Fan
Package Includes:
SU1500XLCD UPS system, PowerAlert software CD and cable, owner's manual with warranty information and EPO (emergency power off) cable